Replacement Instructions for the Condensation Pump and Sensors HP Modular Cooling System

a.
Lift the right side of the bracket up at a slant, and
slide the bracket into the MCS unit.
b. Tighten the four thumbscrews to secure the outer
bracket to the MCS unit.
4. Connect the green and yellow ground bonding wire to
ground the outer support bracket to the MCS unit.
Replacing the bottom fan unit
1. Align the fan unit to the sliding rails.
CAUTION: The fan unit wei
g
hs 16.8 k
g
(37 lb). Use
extra caution when removing and replacing the top
fan unit because it might be higher than your
shoulders and is heavy and awkward to lift.
2. Slide the bottom fan unit inside the MCS unit on the
sliding rails.
3. Tighten the two thumbscrews to secure the fan unit to the
MCS frame.
4. Using a T-25 Torx driver, secure the horizontal shipping
bracket to the MCS unit by inserting four Torx screws.
Operation checklist
1. If power was disconnected, restore power to the MCS
unit.
a. Open the rear MCS door.
b. Connect the network cable to the RJ-45 connector on
the power inlet box.