Replacement Instructions for the Condensation Pump and Sensors HP Modular Cooling System
c.
Connect the two AC power cables to the power
connectors on the power inlet box.
d. Open the front MCS door.
e. Turn on the AC1 breaker on the AC transfer switch.
f. Turn on the AC2 breaker on the AC transfer switch.
2. Clear all old logs from the web interface to ensure that
any additional alarms are current.
3. Confirm that no additional warning or alarm messages
have been detected by looking at the operator display.
Returning the failed component
Instructions are provided on the return label supplied with the
replacement component. The return label is either in the box
in which the component was shipped or in the plastic pouch
attached to the box.
For further information about the Customer Self Repair
program, see http://www.hp.com/go/selfrepair.