Replacement Instructions for the Flow Meter Paddle-Wheel Sensor HP Modular Cooling System
2.
Secure the air sealing plate to the MCS unit by
tightening the two thumbscrews.
3. Connect the condensation hose to the condensation
pump by inserting it into the plastic collar quick connect
on the condensation pump.
Relocating the power inlet box
back into position
1. Lower the right side of the power inlet box until it is back
into the horizontal position.
2. Push the power inlet box back into the MCS unit until it
locks in place.
3. Replace the outer support bracket.
a. Lift the right side of the bracket up at a slant, and
slide the bracket into the MCS unit.
b. Tighten the four thumbscrews to secure the outer
bracket to the MCS unit.
4. Connect the green and yellow ground bonding wire to
ground the outer support bracket to the MCS unit.