Replacement Instructions for the Heat Exchanger Unit HP Modular Cooling System
5. Connect the condensation hose to the heat
exchanger unit.
6. Using the counter hold wrench to hold the fitting in place
and the water hose fitting wrench to tighten the water
hose (both wrenches are included with your original
MCS unit), connect the In and Out water hoses to the
heat exchanger unit.
7. Connect the temperature sensor connector to the heat
exchanger unit.
Replacing the air deflector
plate
1. Reattach the ground bonding wires to the air
deflector plate.
2. Align the two screw holes on the air deflector plate to
the two screw holes inside the MCS unit.
3. Secure the air deflector plate to the MCS unit by
tightening the two thumbscrews in the two screw holes.
Replacing the fan unit
1. Align the fan unit to the sliding rails.
CAUTION: The fan unit wei
g
hs 16.8 k
g
(37 lb). Use
extra caution when removing and replacing the top
fan unit because it might be higher than your
shoulders and is heavy and awkward to lift.
2. Slide the fan unit onto the sliding rails inside the
MCS unit.