Replacement Instructions for the Heat Exchanger Unit HP Modular Cooling System
3.
Tighten the two thumbscrews to secure the fan unit to the
MCS frame.
NOTE: The number of horizontal brackets varies
depending on the position of the fan unit (top,
middle, or bottom).
4. Using a T-25 Torx driver, secure the horizontal shipping
bracket to the MCS unit by inserting four Torx screws.
5. Complete the operation checklist.
Operation checklist
1. Clear all old logs from the web interface to ensure that
any additional alarms are current.
2. Confirm that no additional warning or alarm messages
have been detected by looking at the operator display.
Returning the failed component
Instructions are provided on the return label supplied with the
replacement component. The return label is either in the box
in which the component was shipped or in the plastic pouch
attached to the box.
For further information about the Customer Self Repair
program, see http://www.hp.com/go/selfrepair.