Replacement Instructions for the Magnetic Solenoid Valve HP Modular Cooling System

4.
Connect the green and yellow ground bonding wire to
ground the outer support bracket to the MCS unit.
Replacing the bottom fan unit
1. Align the fan unit to the sliding rails.
CAUTION: The fan unit wei
g
hs 16.8 k
g
(37 lb). Use
extra caution when removing and replacing the top
fan unit because it might be higher than your
shoulders and is heavy and awkward to lift.
2. Slide the bottom fan unit inside the MCS unit on the
sliding rails.
3. Tighten the two thumbscrews to secure the fan unit to the
MCS frame.
4. Using a T-25 Torx driver, secure the horizontal shipping
bracket to the MCS unit by inserting four Torx screws.
Operation checklist
1. If power was disconnected, restore power to the MCS
unit.
a. Open the rear MCS door.
b. Connect the network cable to the RJ-45 connector on
the power inlet box.
c. Connect the two AC power cables to the power
connectors on the power inlet box.
d. Open the front MCS door.