Replacement Instructions for the Water Group Controller HP Modular Cooling System

CAUTION: To reduce the risk of the servers
overheating, open all of the rack doors of each rack
attached to the MCS unit while completing the
following procedures to increase air flow within
the rack.
Powering down the MCS unit
1. Open the front MCS door.
2. Turn off the AC1 and AC2 breakers on the AC
transfer switch.
3. Open the rear MCS door.
WARNING: To reduce the risk of electric shock or
damage to the equipment:
Do not disable the power cord grounding plug.
The grounding plug is an important safety
feature.
Plug the power cord into a grounded (earthed)
electrical outlet that is easily accessible at all
times.
Unplug the power cord from the power supply to
disconnect power to the equipment.
Do not route the power cord where it can be
walked on or pinched by items placed against it.
Pay particular attention to the plug, electrical
outlet, and the point where the cord extends from
the storage system.
4. Disconnect the two AC power cables from the power
connectors, labeled Primary and Secondary, on the
power inlet box.
5. Disconnect the network cable from the RJ-45 connector
on the power inlet box.
Required tools
To complete the following steps, you will need:
T-25 Torx driver
8 mm socket
Flat-head screwdriver
Removing the AC transfer
switch
1. Power down the MCS unit ("Powering down the MCS
unit" on page 2).
2. Open the front MCS door.
3. Slide the metal AC transfer switch box out toward you
on the sliding rails.