Replacement Instructions for the Water Temperature Sensor HP Modular Cooling System
3.
Loosen the two thumbscrews on the bottom of the
fan unit.
CAUTION: The fan unit wei
g
hs 16.8 k
g
(37 lb). Use
extra caution when removing and replacing the top
fan unit because it might be higher than your
shoulders and is heavy and awkward to lift.
4. Pull the fan unit out toward you, and remove it from the
MCS unit.
To replace this component, see "Replacing the bottom fan unit
(on page 9)."
Relocating the power inlet box
1. Disconnect the green and yellow ground bonding wire
grounding the outer support bracket to the MCS unit.
2. Remove the outer support bracket.
a. Loosen the four thumbscrews securing the outer
support bracket to the MCS unit (1).
b. Lift the right side of the bracket up at a slant, and pull
the bracket out of the MCS unit (2).
IMPORTANT: Do not disconnect any of the internal
electrical connections to the power inlet box.
3. Pull the power inlet box toward you until it stops.
4. Set the power inlet box aside in the side cavity by lifting
the right side of the power inlet box up until the box sits
vertically on the left side of the MCS unit.
To replace this component, see "Relocating the power inlet