Replacement Instructions for the Water Temperature Sensor HP Modular Cooling System
Removing the air sealing plate
1. Disconnect the condensation hose from the condensation
pump by pressing in the plastic collar quick connect on
the condensation pump.
2. Loosen the two thumbscrews securing the air sealing
plate to the MCS unit.
3. Slide the air sealing plate out of the MCS unit.
To replace this component, see "Replacing the air sealing
plate (on page 8)."
Removing the air deflector
plate
1. Loosen the two thumbscrews securing the air deflector
plate to the MCS unit.
2. Disconnect the green and yellow ground bonding wire.
3. Lift the air deflector plate up, tilt it to an angle, and pull it
out toward you.
To replace this component, see "Replacing the air deflector
plate (on page 8)."
Removing the condensation
pump and sensors
1. Disconnect the AC power cable from the condensation
pump.