Replacement Instructions for the Water Temperature Sensor HP Modular Cooling System
2.
Secure the air sealing plate to the MCS unit by
tightening the two thumbscrews.
3. Connect the condensation hose to the condensation
pump by inserting it into the plastic collar quick connect
on the condensation pump.
Relocating the power inlet box
back into position
1. Lower the right side of the power inlet box until it is back
into the horizontal position.
2. Push the power inlet box back into the MCS unit until it
locks in place.
3. Replace the outer support bracket.
a. Lift the right side of the bracket up at a slant, and
slide the bracket into the MCS unit.
b. Tighten the four thumbscrews to secure the outer
bracket to the MCS unit.
4. Connect the green and yellow ground bonding wire to
ground the outer support bracket to the MCS unit.
Replacing the bottom fan unit
1. Align the fan unit to the sliding rails.
CAUTION: The fan unit weighs 16.8 kg (37 lb). Use
extra caution when removing and replacing the top
fan unit because it might be higher than your
shoulders and is heavy and awkward to lift.