HP StorageWorks 60 Modular Smart Array Enclosure User Guide

Setup 15
Do not allow the overall system AC current load to exceed 80 percent of the branch circuit AC
current rating.
Do not use common power outlet strips for this equipment.
Provide a separate electrical circuit for each power supply in the storage enclosure.
Electrical grounding requirements
The storage enclosure must be grounded properly for proper operation and safety. In the United States,
you must install the equipment in accordance with NFPA 70, 1999 Edition (National Electric Code),
Article 250, as well as any local and regional building codes. In Canada, you must install the equipment
in accordance with Canadian Standards Association, CSA C22.1, Canadian Electrical Code. In all other
countries, you must install the equipment in accordance with any regional or national electrical wiring
codes, such as the International Electrotechnical Commission (IEC) Code 364, parts 1 through 7.
Furthermore, you must be sure that all power distribution devices used in the installation, such as branch
wiring and receptacles, are listed or certified grounding-type devices.
Because of the high ground-leakage currents associated with multiple storage enclosure connected to the
same power source, HP recommends the use of a power distribution unit (PDU) that is either permanently
wired to the building’s branch circuit or includes a nondetachable cord that is wired to an industrial-style
plug. NEMA locking-style plugs or those complying with IEC 60309 are considered suitable for this
purpose. Using common power outlet strips for the storage enclosure is not recommended.
Rack warnings
WARNING: To reduce the risk of personal injury or damage to the equipment, be sure
that:
The leveling jacks are extended to the floor.
The full weight of the rack rests on the leveling jacks.
The stabilizing feet are attached to the rack if it is a single-rack installation.
The racks are coupled together in multiple-rack installations.
Only one component is extended at a time. A rack may become unstable if more than
one component is extended for any reason.
WARNING: To reduce the risk of personal injury or equipment damage when unloading
a rack:
At least two people are needed to safely unload the rack from the pallet. An empty
42U rack can weigh as much as 115 kg (253 lb), can stand more than 2.1 m (7 ft)
tall, and may become unstable when being moved on its casters.
Never stand in front of the rack when it is rolling down the ramp from the pallet.
Always handle the rack from both sides.
Shipping contents
When unpacking the MSA60, locate the following items:
MSA60
Rack mounting hardware kit
Power cords (2)
SAS cable
Documentation kit