HP MSR4000 Router Series Installation Guide

5
Install a special lightning arrester at the input end of outdoor signal lines (for example, E1/T1 line)
to which interface modules of the router are connected to enhance the lightning protection
capability.
Rack-mounting
Before mounting the router in a rack, adhere to the following requirements:
The rack is equipped with a good ventilation system.
The rack is sturdy enough to support the router and its accessories.
For heat dissipation and device maintenance, make sure the front and rear of the rack are at least
0.8 m (2.62 ft) away from walls or other devices, and the headroom in the equipment room is no
less than 3 m (9.84 ft).
Installation accessories
Pre-installation checklist
Table 5 Pre-installation checklist
Item Re
q
uirements
Result
Installation site Ventilation
There is a minimum clearance of 10 cm (3.94 in)
around the inlet and outlet vents for heat
dissipation of the router chassis.
A good ventilation system is available at the
installation site.