HP StorageWorks SAN Director Installation Guide (A7393-90009, May 2007)

Technical specifications198
The environmental specifications listed in Table 52 on page 204
Electrical interference less than the levels stated in the standards listed in Table 53 on page 205.
If the 4/256 SAN Director will be installed in an EIA rack, ensure the following:
All equipment installed in the rack has a reliable branch circuit ground connection, and does
not rely on a connection to a branch circuit, such as a power strip.
The rack is balanced and mechanically secured to provide stability in the event of an
earthquake.
Additional equipment does not exceed the rack’s weight limits.
Power specifications
WARNING! Disconnect both power cables to remove all power from the 4/256 SAN Director.
The power subsystem is a redundant +48V DC power distribution system with a provision for up to
four 1000-watt, 48V DC bulk power supplies. Four bulk power supplies produce the intermediate
distribution voltage in the distributed power system.
The power specifications listed in Table 50 are calculated for fully loaded systems with four power
supplies. A fully loaded system has eight FC4-32 port blades, two CP4 cards, and three blower
assemblies.
NOTE: HP ships two power supplies standard. Users can purchase optional Director power
supplies for the remaining two slots as required.
.
Table 50 Power specifications
Specification Value
Input voltage A fully loaded switch requires a maximum of 750 Volt-Amps
This results in a main current of 3.2 amps at 240V AC line voltage or 3.6
amps at 208V AC line voltage.
The rated AC input range is 180 to 264V AC.
Supported power range Nominal: 200 to 240 VAC, single phase
Input frequency range 47-63 Hz
Power supplies (each) Output voltages: 48V at 20 amps; 12V at 4 amps
Maximum output power: 1000 watts