HP Netserver LH 4r Rack Cabling Guide

Chapter 3 Cabling Reference Information
46
Table 3-1. LH 4r Plugs and Receptacles Reference
Item 100/120VAC 200/208VAC 230/240VAC
LH 4r, RS/8 Line Cord
8120-8378
NEMA 5-15
plug, 90" (2.3 m),
16 AWG
See next line. See next line.
LH 4r, RS/8 PDU Jumper Cord
Model No.
See previous
line.-
E7742A
90 inch
(2.3 m)
E7742A
90 inch
(2.3 m)
PDU Model No.
E7675A E7671A alone
or with E7672A
E7671A alone
or with E7672A
Can PDUs be "Daisy Chained"?
No Yes, 10A plugs
into 16A
Yes, 10A plugs
into 16A
PDU Linecord style
Detachable Detachable Detachable
Recommended PDU linecord for
installations with recommended
UPS
E7802A, 4.5m
NEMA 5-20P
plug, C19 end
Notes 1, 2
E7803A, 4.5m,
with NEMA L6-
20P plug to C19
E7804A, 4.5m,
with IEC C20 to
C19
Alternate PDU linecord for
installations without a UPS
E7802A, 4.5m
NEMA 5-20P to
C19
Note 1, 3
E7803A, 4.5m,
NEMA L6-20P
to C19
E7806A, 4.5 m,
C19 to
unterminated
E7805A
4.5 m with
NEMA L6-30P
to C19
E7804A,
4.5 m with C20
to C19
E7806A 4.5m
unterminated to
C19
Input 2.5m with
CEE7/7 for
Europe and 13
amp fused plug
for UK
UPS APC Model Number
NS2200RM3U
Notes 1, 2
NS3000RMT3U NS2200RMI3U
or
NS3000RMI3U
Note 1. For 100 VAC systems, separately orderable cables and UPS are available.
Note 2. Consult American Power Corporation (APC) for model number of 100 VAC unit.
Note 3. For 100 VAC, consult local electrical codes and order a PDU power cord with
appropriate connector from American Power Corporation (APC).