HP Netserver LT 6000r Rack Cabling Guide

Chapter 2 Rack Cabling References
16
Figure 2-1. Three-way Cord to Allow Single Power Input
Power Considerations for the HP NetServer LT 6000r
The HP NetServer LT 6000r can be configured in a wide range of voltages from
100 - 240 VAC. Power supply (UPS) and distribution (PDU) components are
available to support these configurations. A Redundant Switch is also available.
Details of power considerations for the HP NetServer LT 6000r include:
An optional power cord is available at all voltages to allow the three
input receptacles on the rear of the LT 6000r to be powered by a single
attachment to the power distribution unit.
The appropriate power cord(s) for each server is (are) shipped
according to voltage requirements; refer to Table 2-2 for details.
Each power supply installed in the HP NetServer LT 6000r uses a
separate jumper cord.
100/120, 200/208, and 220/230/240 VAC configurations are available
for the U. S. market
Either 200/208 VAC or 220/230/240 VAC configurations are available
for international markets.
Uninterruptible Power Supply (UPS) models rated at 3000 Volt Amps
(2250 Watts) are available for each voltage range, and a 2200 Volt
Amp (1600 Watts) UPS is available for 110/120 and 220/230/240 VAC
(see Table 2-1).
At 100/120 VAC, a wide range Power Distribution Unit (PDU) rated at
16 A is available (9 outlets).
for both 200/208 and 220/230/240 voltages, a wide range Power
Distribution Unit (PDU) model rated at 16 Amps is available; a
10-Amp-rated extension PDU is also available (see Figure 2-2)