HP Netserver LT 6000r Rack Cabling Guide

Chapter 3 Procedure for Connecting and Routing Cables to the LT 6000r
45
Table 3-2. 208 VAC Components
Component
1
Model
Power
(VA)
Power
(W)
Current
(A)
2
PDU E7675A N/A N/A max 16
HP NetServer
Mass Storage Unit
Rack Storage/12
is D5989A
Rack Storage/
12FC is D5991A
541 530 4.5
HP Console Switch J1497B 42 29 0.2
Note 1. More ratings are listed in Table 2-8. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2. Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 208 VAC Configuration
Figure 3-6 shows a UPS connected to the power mains through a captive cord
terminated with an L6-20P plug. The UPS has five receptacles for use in the
rack: two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and
one L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a
detachable cord with an L6-20P plug. This cord connects to the PDU with an IEC
320 C-19 plug. The 208 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13
receptacles. A second PDU (E7670A) is available, which can be daisy-chained to
the 16-amp unit, providing ten more C-13 receptacles.