HP Netserver LT 6000r Rack Cabling Guide

Chapter 3 Procedure for Connecting and Routing Cables to the LT 6000r
48
Table 3-3. 230/240 VAC PDU Power and Current
Component
1
Model
Power
(VA)
Power
(W)
Current
(A)
2
PDU E7675A N/A N/A max 16
HP NetServer
Mass Storage Unit
Rack Storage/12
is D5989A
Rack Storage/
12FC is D5991A
541 530 4.5
HP Console Switch J1497B 42 29 0.2
Note 1. More ratings are listed in Table 2-9. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2. Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 230/240 VAC Configuration
Figure
3-7 shows a UPS connected to the power mains through an attached power
cord (appropriate cords are supplied for each country). The UPS has eight IEC
320 receptacles for use with the rack jumper cords. The E7671A
PDU connects to
the UPS via a detachable line cord, which connects to the PDU via a C-19 plug.
This cord connects to the UPS with a C-20 plug. The 200/240 VAC
PDU has two
IEC 320, C-19 and six IEC 320, C-13 receptacles for connecting rack jumper
cords.