HP Netserver Service Handbook, Volume 3 - High-End
47
Specifications
Video
Integrated 1024x768sx256 60-75hz Video, 1 meg video RAM (Cirrus
5446)
Expansion Slots
Total PCI Buses:3, Total I/O slots:10
• 4 64-bit PCI Full Length on PCI 2 (Hot Swap)
• 5 32-bit PCI Full Length on PCI 1
• 1 shared 32-bit PCI/ISA Full Length on PCI 0
Dimensions
System dimensions
12.25 in. high x 17.5 in. wide x 28 in. deep
(31.1 cm high x 44.5 cm wide x nn 71.1 deep)
Rack space
7 EIA units
System weight
130 lb. (59 kg)
Cooling Specifications
Maximum heat output
3675 BTU/hour
Operating temperature
41 to 95 degrees F (5 to 35 degrees C)
Operating humidity
20% to 80% Rh
Power Specifications
Voltage and frequency
200-240 VAC; 50/60 Hz
Maximum continuous
power input
1100 W for a four-CPU configuration; 5.6 A at 200/208 V, 4.9 A at
230/240 V.
Maximum inrush current
150 A for 4 ms
Delayed action circuit
breaker recommended
North America: a 20 A minimum circuit is to be used with one NEMA
AB1 class 14B breaker for each 16 A power distribution unit (PDU)
that is connected to an HP NetServer LXr 8000.
Europe (a single server in a rack): use a 16 A-minimum circuit with
one IEC MCB C-type breaker for each 16-amp PDU.
Europe (multiple servers in a rack): use a 16-amp-minimum circuit with
one IEC MCB D-type breaker for each 16 A PDU.
Power availability
1500 DC watts continuous
NOTE Some local electrical codes do not allow a 16-amp device to be connected to a 16-
amp service. Consult a qualified electrician or local regulatory authority before
beginning electrical site preparation.