HP NetServer LH 3000r Rack Cabling Reference Guide
Notice The information contained in this document is subject to change without notice. Hewlett-Packard makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Hewlett-Packard shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material.
Contents 1 Preparation for Cabling the NetServer LH 3000r........................................ 1 About Cabling the LH 3000r........................................................................... 1 Before You Use this Reference Guide ....................................................... 1 The HP NetServer LH 3000r...................................................................... 1 Site Preparation.............................................................................................
Contents Overview of LH 3000r Data Connections ................................................. 32 Attach Data Cables to the Server............................................................. 35 Attach Data Cables to Other Components ............................................... 37 Step 3: Cable the LH 3000r for Power.......................................................... 37 Attaching Server and Component Power Cables......................................
1 Preparation for Cabling the NetServer LH 3000r About Cabling the LH 3000r NOTE A checklist for the cabling process is included in Appendix A. Before You Use this Reference Guide This HP NetServer LH 3000r Cabling Reference Guide assumes that you have the rack assembly process completed, have mounted the HP NetServer LH 3000r, and are ready to cable the components in the rack enclosure. If you want a high-level checklist to use in this process, see Appendix A.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r Figure 1-1. The HP NetServer LH 3000r Site Preparation You may want to copy and use the site preparation checklist in this section (Table 1-1). Doing so before you begin to install and cable the NetServer may reveal actions you can take to support your success. Also be sure to read the section on site preparation of circuit breakers.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r Site Preparation Checklist Table 1-1.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r Table 1-1. Site Preparation Checklist (Continued) Environment and Space Requirements Must meet OSHA, local code, and HP specifications for safety and supportability (3 feet minimum access in front and rear of electrical cabinets) Side access of 24 inches improves cable routing and management Optimal: 24 hour air conditioning (68 - 72 deg. F; 20 - 22 deg.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r standby mode. Inrush current is much greater than the server’s normal operating needs. Generally, your external AC power source can handle the inrush current. However, if you install several HP NetServers on one circuit, precautions are necessary. For instance, if there is a power failure and power is then restored all the servers immediately begin to draw inrush current at the same time.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r Prevent Electrical Shock WARNING Ensure site electrical circuits have reliable earth grounding. Never operate products in any rack enclosure with the ground connector disconnected. Although leakage current from any one device may be minimal, cumulative leakage current of equipment mounted in a rack may exceed 5mA, and could reach 15mA. This level of current can be dangerous, unless a reliable earth ground is in place.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r Generic Rack Assembly Steps Suggested Method for Building an HP NetServer Rack Installation 1.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r 3. Prepare Rack Enclosures for Assembly WARNING A tip-over hazard exists. Rack enclosures are shipped upright and are top-heavy. Never move enclosures without adequate equipment and assistance. Use caution to prevent rack from falling over and causing potential damage or injury. If you receive pre-configured units, follow assembly instructions from the supplying organization first, if you have them.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r WARNING When equipment is mounted on slides, a tip-over hazard exists. Always take the precautions listed below: • Extend or bolt on the anti-tip foot for each rack before mounting equipment on slides. • Never extend more than one piece of slide-mounted equipment at a time. • Reduce weight by removing power supplies. • Always use the rack mounting handles that are shipped on rack optimized units as shown in accompanying instructions. 4.
Chapter 1 NOTE Preparation for Cabling the HP NetServer LH 3000r Older racks (with the words "HP Systems" on the nameplate) may require that enclosures to be tied together before any components are mounted inside them. To avoid problems, if older rack versions are to be tied together, do so before installing slide members, rails, shelves, units, or other hardware. Otherwise, you may have to remove components from the rack to gain access to the tie-bolt locations. 2.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r 3. Install the Redundant Switch, if you have one, in one of the configurations shown in Appendix B. 9. Mount Component in the Rack Plan Component Locations Use the original ordering information to locate where each component goes in the rack. If the original ordering information is not available, use HP rack configuration tools to plan the location of each component.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r NOTE For both safety and accessibility, always start assembly at the bottom of the rack and work upward. 4. Be sure to locate and place rack nuts along the front outside face of the vertical column before placing each component on its rails or base. The pre-positioning of rack nuts allows the front of the component to be secured to the front of the rack.
Chapter 1 Preparation for Cabling the HP NetServer LH 3000r • Determine configurations for and mount the PDU (Power Distribution Unit or Units). Connect the LH 3000r Data Cables to Peripheral Components • Plan where data connections are to be made. • Attach data cables to the server. Mark the ends of data cables with colored tie-wraps and labels supplied with each server. This simplifies attaching cables later in the procedure.
2 Rack Cabling References Rack Configuration Tools Selected reference material derived from HP’s rack configuration tools is published in this chapter for convenience including the following: • necessary and optional components • rack power subsystem configuration and placement • current and power requirements • discussion of component location in the rack • routing cables through the Cable Management Arm and Cable Guide • cooling requirements and air flow HP rack configuration tools are available on the w
Chapter 2 Rack Cabling References Power Cabling References and Guidelines Power Considerations for the HP NetServer LH 3000r The HP NetServer LH 3000r can be configured in a wide range of voltages from 100 - 240 VAC. Power supply (UPS) and distribution (PDU) components are available to support these configurations. A Redundant Switch is also available.
Chapter 2 Rack Cabling References Power Cables and Components Available When components are installed in a rack, a power supply subsystem for the rack is required.
Chapter 2 Rack Cabling References Table 2-2. LH 3000r Plugs and Receptacles Reference 100/120 VAC 200/208 VAC 230/240V LH 3000r Jumper Cord 8120-8378 NEMA 5-15 plug, 90" (2.3 m), 16 AWG included C13 to C14, 2.5 m included C13 to C14, 2.5 m RackStorage/12 /12FC and PDU Jumper Cord E7742A, 90 inch (2.5 m), C13 to C14 E7742A, 90 inch (2.5 m), C13 to C14 E7742A, 90 inch (2.5 m), C13 to C14 PDU Model No.
Chapter 2 Rack Cabling References Notes to Table 2-2. Note 1. For 100 VAC Systems, separately-orderable cables and UPS are available from American Power Conversion Corporation. Note 2. Consult American Power Conversion Corporation (APC) for model number of 100 VAC unit. Note 3. For 100 VAC, consult local electrical codes and order a PDU power cord with appropriate connector from American Power Conversion Corporation (APC). Note 4.
Chapter 2 NOTE Rack Cabling References The extension PDU (E7670A) only increases the number of available receptacles. The total current carrying capacity still is limited to 16 amps for the two PDUs, when daisy chained. In addition, the extension PDU is limited to carrying only 10 amps. Placement of PDU To determine where the PDU mounts, eliminate positions directly behind equipment listed in Table 2-3. (PDUs conflict with these units when mounted in the same space).
Chapter 2 Rack Cabling References Power Distribution Unit Types 200/240 VAC Wide Range, 10-Amp together with 16-Amp and Jumper Cord Available as E7672A 100/120 VAC, 16-Amp, Order as E7675A (Not used with 200/240 VAC models) 200/240 VAC, 16-Amp, Wide Range, Order Standalone as E7671A, Power Cord Separately Orderable Figure 2-1. PDU Configurations The 200/240 VAC, wide-range Power Distribution Unit (PDU) can be mounted in several configurations with the LH 3000r.
Chapter 2 Rack Cabling References How to Position the PDU Count the receptacles needed for each unit in the rack, notice where the PDUs can be most conveniently located, and decide whether to orient the PDU vertically or horizontally.
Chapter 2 Rack Cabling References Guidelines for Powering the LH 3000r in a Rack Four Possible 200/240 VAC Wide Range PDU Configurations Use of four possible 200/240 VAC PDU configurations depends upon the power requirements of the devices in the rack. Table 2-4 shows how to determine how many PDUs are supplied with each rack configuration. In configurations that use a wide-ranging 10-amp PDU, it will always be plugged into a wide ranging 16-amp PDU. Table 2-4.
Chapter 2 Rack Cabling References 10-amp PDU may not provide sufficient receptacles. In this case, use the Y-cable to connect HP Rack Storage/12 or Rack Storage/12FC units to the PDUs. (b) When required, a pair of Y-cables are supplied per pair of Rack Storage/12 or Rack Storage/12FC units. That is, two Y-cables are supplied for two units.
Chapter 2 Rack Cabling References Table 2-6. 100 VAC Power and Current: Approximate Current Requirements of Rack Optimized Devices and Components Device (Notes 1, 2, 3) HP NetServer LC 2000r Input Power (VA) Input Power (W) 100v IRMS (Amps) 545 540 5.5 HP NetServer LH 3000r 833 825 8.3 HP NetServer LH 6000r 1177 1166 11.7 HP NetServer LT 6000r 833 825 8.3 HP NetServer LPr 530 305 5.3 - - Not Supported HP NetServer LH 4r 1170 1140 11.
Chapter 2 Rack Cabling References Table 2-7. 120 VAC Power and Current: Approximate Current Requirements of Rack Optimized Devices and Components Device (Notes 1, 2, 3) HP NetServer LC 2000r Input Power (VA) Input Power (W) 120v IRMS (Amps) 531 525 4.5 HP NetServer LH 3000r 815 806 6.7 HP NetServer LH 6000r 1153 1141 9.5 HP NetServer LT 6000r 815 806 6.7 HP NetServer LPr 552 295 4.6 - - Not Supported HP NetServer LH 4r 1160 1130 9.
Chapter 2 Rack Cabling References Table 2-8. 200/208 VAC Power and Current: Approximate Requirements of Rack Optimized Devices and Components Device (Notes 1, 2, 3) Input Power Input Power (VA) (W) 208v IRMS (Amps) HP NetServer LC 2000r 516 506 2.5 HP NetServer LH 3000r 792 777 3.7 HP NetServer LH 6000r 1120 1099 5.3 HP NetServer LT 6000r 792 777 3.7 HP NetServer LPr 640 285 3.2 HP NetServer LXr 8000 and LXr 85004 1121 1077 5.6 HP NetServer LH 4r 1130 1100 5.
Chapter 2 Rack Cabling References Table 2-9. 230/240 VAC Power and Current: Approximate Requirements of Rack Optimized Devices and Components Iput Power (VA) Input Power (W) 230/240v IRMS (Amps) HP NetServer LC 2000r 514 504 2.3 HP NetServer LH 3000r 790 774 3.4 HP NetServer LH 6000r 1117 1095 4.8 HP NetServer LT 6000r 790 774 3.4 HP NetServer LPr 644 285 2.8 HP NetServer LXr 8000 and 85004 1121 1077 4.9 HP NetServer LH 4r 1120 1100 4.9 HP NetServer LH 3r 650 626 2.
Chapter 2 Rack Cabling References Data Cabling References and Guidelines A series of positioning rules is used in the HP rack configuration tools to help determine where each component is placed in multiple rack layouts. Key Cabling Guidelines Used in Developing a Rack Layout The following discussion is intended to support your understanding of how your rack order was arrived at. It also discusses how rack layouts affect the attachment and routing of cables.
Chapter 2 Rack Cabling References • Ensure the monitor cables and mouse cables are long enough to allow the NetServer to be extended at the same time the keyboard tray is pulled out. Use locally available extensions if necessary. • The mounting distances provided in rack configuration tools assume cables between the servers and connected devices provide for the Cable Management Arm (for the LH 3000r).
3 Procedure for Connecting and Routing Cables to the LH 3000r Step 1: Prepare to Cable the HP NetServer LH 3000r Assess How Components Will be Connected to the Server You may find the following steps to be helpful before you begin cabling: • Review the layout of the rack installation generated with Hewlett-Packard rack configuration tools, such as Rack Assistant (available at www.hp.com/go/netservers).
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Mount Power Distribution Units Plan the location of the Power Distribution Unit or Units (PDU) by reference to amperage, power, and the number of receptacles. See Chapter 2, the section entitled "Wide Range PDU Configurations," particularly Table 2-4. Follow mounting instructions included with your power distribution units. Notice these cannot be installed behind some equipment. See Table 2-3.
Chapter 3 HP NetServer LH 3000r Procedure for Connecting and Routing Cables to the LH 3000r Rack Storage/12 Dashed Lines Indicate Dual Bus Configured Storage Figure 3-1. Overview of Data Cabling of the HP NetServer LH 3000r to an HP Rack Storage/12 NOTE Figure 3-1 shows an HP Console Switch, which is not necessary for configuring the system, but is shown for informational purposes. NOTE The configuration in Figure 3-1 requires 1 UPS and 1 PDU at 120 V, 200/208 V, and at 220/230/240 V.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Figure 3-2 shows an HP NetServer LH 3000r connected in Dual Active Mode to a Rack Storage/12FC. HP 6-Port Hub with GBICs HP NetServer LH 3000r HP Rack Storage/12FC with GBICs HP Rack Storage/12 HP Rack Storage/12 Figure 3-2.
Chapter 3 NOTE Procedure for Connecting and Routing Cables to the LH 3000r The configuration in Figure 3-2 requires different power system configurations at different voltages, as shown below: Voltage Power System Requirements 100 2 PDUs, 3000 VA UPS 120 2 PDUs, 3000 VA UPS 200/208 1 PDU, 3000 VA UPS 230/230/240 1 PDU, 3000 VA UPS For more information on data cabling with the Rack Storage/12FC, see the HP Rack Storage/12 FC Installation Guide. Attach Data Cables to the Server 1.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Rear View of Rack Figure 3-3. Connecting the Data Cables between the LH 3000r and Rack Storage/12FC 2. Locate any network and remote management connections from hubs, routers and other sources and connect their cables to corresponding server connectors. 3. Locate the cable that will attach the serial port on the Uninterruptible Power Supply (UPS) (if present) and plug in the server end. 4.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r and monitor for more than one server, attach the cables for the HP Console Switch to the server ports for video, mouse, and keyboard ports. Check Whether Cable Lengths Limit Distances between the Server and Storage Sometimes data cable length or availability limits the distance between a peripheral component (such as the UPS or video monitor) and its associated server.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r 4. For the sake of easy access to the rear of each component, route the associated power cords within the same space (the same set of EIA Units) where the component is located. Excess cord can be handled by coiling and tie wrapping unneeded length, and hanging it in the space at the side of the component it connects. When doing so, be sure you allow sufficient slack for access.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Figure 3-4. Power Connection Locations on a Typical Rack (Rear View) 100/120 VAC Rack Power Configurations The 120 VAC PDU power configurations are detailed in the recommendations shown below and in Table 3-1 and Figure 3-5. NOTE 100 VAC configurations are the same as 120 VAC, except for the UPS and the cable which connects the PDU to it. See Table 3-1 and the notes which accompany it.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Connecting the PDU 120 VAC Configuration The Power Distribution Unit (PDU) plugs into the Uninterruptible Power Supply (UPS) if one is present. The 120 volt PDU uses an E7802A detachable cord with a NEMA 5-20P connector for connections to the receptacles on the right-hand side (viewed from the rear) of the UPS. It connects to the PDU through a C19 connector. CAUTION It is not possible to plug one 16-amp, 120 VAC PDU into another.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Table 3-1. 120 VAC Components Component1 Model Power (VA) Power (W) Current (A)2 E7675A N/A N/A max 16 HP NetServer LH 3000r D8230A, 533 MHz, 512 MB D8238A, 600 MHz, 256 MB D8246B, 667 MHz, 256 MB 531 525 4.5 HP NetServer Mass Storage Unit Rack Storage/12 is D5989A Rack Storage/12FC is D5991A 541 530 4.5 J1497B 42 29 0.2 PDU HP Console Switch Note 1 More ratings are listed in Table 2-7.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Recommended 100-120 VAC Power Configuration HP NetServer LH 3000r Jumper Cables NEMA 5-15P to IEC 320 C-14 Mass Storage Unit Uninteruptible Power Supply NEMA 5-20P Detachable Cord NEMA 5-20P to IEC 320 C-20 110 VAC, 16-Amp PDU Figure 3-5.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Figure 3-5 shows a UPS connected to the power grid through a captive cord with a NEMA 5-20P. The UPS has receptacles for use in the rack: two (on the right rear) NEMA 5-20R and six NEMA 5-15R. The PDU connects to the UPS via a detachable cord (NEMA 5-20P to an IEC 320 C20). The 120 VAC PDU has nine NEMA 5-15R and one (at the right) IEC 320 receptacle.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Table 3-2. 208 VAC Components Component1 Model Power (VA) Power (W) Current (A)2 208 VAC PDU E7671A or E7672A N/A N/A max 16 HP NetServer LH 3000r D8230A, 533 MHz, 512 MB D8238A, 600 MHz, 256 MB D8246B, 667 MHz, 256 MB 516 506 2.5 HP NetServer Mass Storage Unit Rack Storage/12 is D5989A Rack Storage/12FC is D5991A 522 512 2.6 J1497B 42 29 0.2 HP Console Switch Note 1 More ratings are listed in Table 2-8.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Recommended 208 VAC Power Configuration for the LH 3000r HP NetServer LH 3000r Rack Mass Storage Unit Jumper Cable Supplied with NetServer Uninterruptible Power Supply Jumper Cables Supplied with Mass Storage Units Captive L6-20P Cord Cable Orderable for 16-Amp PDU, E7801A L6-20P to IEC 320 C19, 2.5 m (Other Configurations Possible) 16-Amp Power Distribution Unit, E7671A Figure 3-6.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r 230/240V PDU Rack Power Configurations Configurations for the 230/240 VAC, PDU options are shown in the text below, Table 3-3, and Figure 3-7. 230/240 VAC Power Configuration In a country with a 230/240 VAC power system, the wide range (200/240 V) PDU model E7671A is required.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Table 3-3. 230/240 VAC PDU Power and Current Component1 Model Power (VA) Power (W) Current (A)2 200/240 VAC PDU E7671A or E7672A N/A N/A max 16 HP NetServer LH 3000r D8230A, 533 MHz, 512 MB D8238A, 600 MHz, 256 MB D8246B, 667 MHz, 256 MB 514 504 2.3 HP NetServer Mass Storage Unit Rack Storage/12 is D5989A Rack Storage/12FC is D5991A 518 507 2.3 J1497B 42 29 0.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Recommended 230/240 VAC LH 3000r Configuration HP NetServer LH 3000r Mass Storage Unit Jumper Cable Supplied with NetServer Jumper Cables Supplied with Mass Storage Units Uninterruptible Power Supply Captive Unterminated Cord to be Terminated Locally Cable Orderable for 16-Amp PDU, E7798A, IEC 320 C19 to C20, 2.5 m (Other Configurations Possible) 16-Amp Power Distribution Unit E7671A Figure 3-7.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Redundant Power Configuration Dual Power Supply Example A dual power supply configuration can be created by ensuring that two different branch circuits feed two different Uninterruptible Power Supplies, which in turn power two PDUs. Figure 3-8 shows a dual power cabling example. This example shows two LH 3000r units powered by two PDUs and two UPS units.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r High Density Configuration High Density Configuration Example A high density configuration is illustrated in Figure 3-9. For this example, one 41EIA Unit Rack (a 2 meter HP Systems or HP System/E rack) is completely filled with power supplies, servers, and storage units. Two mass storage units “sandwich” each NetServer. Branch Circuit A Branch Circuit B Figure 3-9.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Step 4: Managing and Routing Cables Using the Cable Management Arm and the Cable Guides The HP NetServer LH 3000r has one power input cable for each set of two installed power supplies. Another power cable is needed for the optional redundant power supply. Cables connect external devices and networks to the I/O adapters in the PCI slots.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r A. Begin with the Server all the way in. B. Plug power and data cables into the back of the Server. F. Dress cables through the fingers of the Cable Guide. C. Gather Cables at left Next to Cable Management Arm flange. E. Determine whether to tie wrap cables into the inner and outer sections of the Arm. D. Arrange cables through the inner section of the arm, around the elbow, and through the outer section. Figure 3-10.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r WARNING Before sliding the HP NetServer LH 3000r out of the rack, make sure you extend the anti-tip foot from under the front of the rack. A tip-over hazard exists, so never slide more than one component out of the rack at a time. NOTE Do not remove the screws that hold the slides to the front columns of the rack. Slide the NetServer out by grasping the handle below the LCD control panel. 3.
Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r 4. Loop extra lengths of cable and tie-wrap it alongside the NetServer. Use Cable Guides on the column of the rack to route cables to their destinations. 5. If you use hook-and-loop straps, tighten each of them to ensure they support the cables correctly. Slide the NetServer in carefully making sure cables do not bind, adjust cables and straps as necessary. Repeat until the Cable Management Arm extends and retracts smoothly. 6.
A Cabling Checklist Checklist for the Rack Cabling Process Use the Site Preparation Checklist in Chapter 1 to make sure your site is ready. Read and follow all Rack Assembly and Cabling Warnings in Chapter 1 and in the Assembly Instructions that accompany your HP Rack. Assemble (new) or assess (existing) rack equipment. Check Wattage, Volt Amps, and Amperage to ensure you do not overload your branch circuit breakers or the rack power supply and distribution equipment.
B Considerations in Mounting the Redundant Switch A redundant switch is available from American Power Conversion Corporation (APC) for use in rack installations. Redundant switches can be used to enhance the reliability of rack power systems. This switch can be used with or without a rack-installed Uninterruptible Power Supply (UPS). Table B-1 shows the Redundant Switch in six possible configurations.
Appendix B Considerations in Mounting the Redundant Switch Table B -1. Components for Use with the Redundant Switch and the LH 3000r Item North America: 100/120 VAC Mains North America: 208/240 VAC Mains International1: 230/240V Mains Application with UPS Application with No UPS Application with UPS Application with No UPS Application with UPS Application with No UPS APC Redundant Switch Model No.
Appendix B Considerations in Mounting the Redundant Switch Figure B-1.
Appendix B Considerations in Mounting the Redundant Switch Figure B-2. 120 VAC Configuration of Redundant Switch between PDU and Branch Circuit Note that switches of 200/208 and 230/240 VAC can be mounted in the same way as the 120 VAC models shown. See Table B-1.
Index A air flow in the rack, 30 C Cable Guide ensure installed, 31 cable inventory preparation checklist, 4 cable management ensure the the Cable Guide is in place, 31 mount the Cable Management Arm, 31 planning for, 29 power cords within occupied area, 38 power cords within same EIA unit, 38 Cable Management Arm ensure installed, 31 cable routing cabling guidelines for the LH 3000r, 32 guidelines for server and peripheral connections, 37 overview of guidelines, 29 overview of procedure, 12 cabling SCSI ca
Index due to cable length, 29 power cabling illustration of rack receptacles, 39 procedure, 37 Power Distribution ensure the PDU is mounted, 32 Power Distribution Unit 120 VAC, 16 amp, 19 208 VAC illustration, 42, 45 208 VAC, LH 3000r configuration, 43 208/240 VAC, 10 amp extension, 19 208/240 VAC, 16 amp, 19 230/240 VAC illustration, 46, 48 configuration guidelines, 23 configurations for LH 3000r, 21 determining and balancing load on double PDUs, 38 models, illustration, 21 placement for the LH 3000r rack
Index space requirements checklist, 4 system parameters checklist, 4 T turn on power, 54 U Uninterruptible Power Supply installation, 10 plug in early to charge batteries, 9 unpacking components, 9 rack enclosure, 8 UPS. See Uninteruptible Power Supply.