HP Netserver LH 3000 Rack Cabling Guide

Chapter 2 Rack Cabling References
17
Power Cables and Components Available
When components are installed in a rack, a power supply subsystem for the rack is
required. HP recommends the NetServer LH 3000r be connected as follows:
connected to a Power Distribution Unit (PDU) -- see Figure 2-1
through an Uninterruptible Power Supply (UPS) -- see Table 2-1
to a properly protected branch circuit or circuits -- see "Site Preparation --
Circuit Breakers" in Chapter 1
NOTE A Redundant Switch is available for use between the UPS and
the branch circuit or between the PDU and the branch circuit.
More information is listed in Table 2-2 and in Appendix B.
Table 2-2 lists details of the cables, components, plugs and receptacles for the
rack power supply subsystems for the HP NetServer LH 3000r.
Table 2-1. UPS Models and Power Ratings
Uninterruptible Power Supplies
APC Model
Voltage
Power (VA)
1
Power (Watts)
2
NS3000RM3U
100/200 VAC 3000 2250
NS2200RM3U
100/120 VAC
3
2200 1600
NS3000RMT3U
200/208 VAC 3000 2250
NS2200RMI3U
230/240 VAC 2200 1600
NS3000RMI3U
230/240 VAC 3000 2250
Note 1. Ensure UPS Volt Amps rating is not exceeded. Add power in Volt Amps of each
component and connect no more than those the UPS supports.
Note 2. Also ensure UPS Wattage rating is not exceeded. Add power in Watts of each
component and connect no more than those the UPS supports.
Note 3. Consult American Power Conversion Corporation (APC) for information on 100
V UPS for Japan.