HP Netserver LH 3000 Rack Cabling Guide

Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r
44
Table 3-2. 208 VAC Components
Component
1
Model
Power
(VA)
Power
(W)
Current
(A)
2
208 VAC PDU E7671A or E7672A N/A N/A max 16
HP NetServer
LH 3000r
D8230A, 533 MHz, 512 MB
D8238A, 600 MHz, 256 MB
D8246B, 667 MHz, 256 MB
516 506 2.5
HP NetServer
Mass Storage
Unit
Rack Storage/12 is D5989A
Rack Storage/12FC is D5991A
522 512 2.6
HP Console
Switch
J1497B 42 29 0.2
Note 1 More ratings are listed in Table 2-8. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2 Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 208 VAC Configuration
Figure 3-6 shows a UPS connected to the power mains through a captive cord
terminated with an L6-20P plug. The UPS has five receptacles for use in the rack:
two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and one
L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a
detachable cord with an L6-20P plug. This cord connects to the PDU with an IEC
320 C-19 plug. The 208 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13
receptacles. A second PDU (E7670A) is available, which can be daisy-chained to
the 16-amp unit, providing ten more C-13 receptacles.