HP Netserver LXr Pro8 User Guide

105
A Specifications
Power Requirements
Table A-1. Power Requirements
Voltage and frequency
200-240 VAC; 47-63Hz.
Maximum continuous power
input
1560W
Maximum inrush current
80A for 10 ms
Delayed action circuit breaker
recommended
208/240 60hz: NEMA AB1 20A
220/230/240 50hz -- IEC MCB 16A, type C (single
server per rack) or type D (multiple servers per rack).
Power availability
200W continuous to PCI cards and internal drives
NOTE The HP NetServer LXr Pro8 includes a total of four power
supplies. The system requires three functional supplies at all
times; individual supplies can be hot-swapped.
Space Requirements
Table A-2. Space Requirements
System dimensions
17.5 in. high x 19.0 in wide x 32.1 in deep
(44.5 cm high x 48.6 cm wide x 81.53 cm deep)
Rack space
10 EIA units
Rack clearance
46 in. (117 cm) beyond rear of HP rack (door mounted)
30 in. (76 cm) beyond rear of HP rack (no door)
System weight
170 lb. (76 kg)