HP Netserver LXr 8500 Rack Cabling Guide

Chapter 2 Rack Cabling References
17
Table 2-2. LXr 8500 Plugs and Receptacles Reference
208 VAC Mains 230/240V Mains
LXr 8500 Jumper Cord
included
C19 to C20, 2.5 m
included
C19 to C20, 2.5 m
RackStorage/12 and /12FC
and PDU Jumper Cord
E7742A, 90 inch (2.5 m), C13
to C14
E7742A, 90 inch (2.5 m),
C13 to C14
PDU Model No.
E7671A (16 Amp)
E7672A (16 amp, cord, and
10 amp)
E7671A (16 Amp)
E7672A (16 amp, cord, and
10 amp)
Can PDUs be "Daisy
Chained"?
Yes, 10 amp plugs into 16
amp (use to extend the
number of receptacles)
1
Yes, 10 amp plugs into 16
amp (use to extend the
number of receptacles)
1
PDU Linecord style
Detachable Detachable
PDU linecord for
recommended UPS
E7803A, 4.5m, with NEMA
L6-20P plug to C19
E7804A, 4.0m, with IEC
C20 to C19 plug,
E7803A, 4.5m, NEMA L6-
20P to C19 plug
E7806A, 4.5 m, C19 to
unterminated
E7805A 4.5 m with NEMA
L6-30P to C19
E7804A, 4.5 m, C20 to C19
Alternate PDU linecords
for installations without a
UPS
E7809A, 4.5 m, CEE 7/7 -
C19
2
UPS APC Model Number
NS3000RMT3U NS2200RMI3U or
NS3000RMI3U
APC Redundant Switch
between PDU and Branch
Circuits (No UPS)
SU045-1 with captive L6-20P
line cords and E7803A, 4.5 m,
L6-20P to C19 to PDU
3
SU044-1, C20 inputs,
country-specific C19 cords,
and E7804A, 4 m, C20 to
C19 jumper cord to PDU
4
Redundant Switch between
UPS and Branch Circuit
SU045-1 with captive line
cords, captive UPS L6-20 P
connects to L6-20R in switch
3
SU044-1, C20 inputs,
country-specific C19 cords,
and E7804A, 4 m C20 to
C19 jumper cord to UPS
4
Note 1. Limit the 10-amp PDU to 10 amps of capacity, plug it into the 16-amp PDU, and
limit both together to 16 amps of capacity.
Note 2. The CEE 7/7 cord is fused for 13-amp loads, and limits the PDU to 13 amps of total
supply.
Note 3. The circuit load should be limited to 3000 VA when this switch is used.
Note 4. The circuit load should be limited to 3000 VA when this switch is used.