HP Netserver LP 1000r User Guide

Chapter 8 Rack Mounting the HP Netserver (4-Post)
77
2. Use the masking tape (or marking pen) to mark above the 3rd hole up on
both front columns, as shown in Figure 8-3.
"
#
"
represents
the EIA unit
numbers on the
rack columns.
3rd Hole
From Bottom
1st Hole
From Bottom
Mark this face of
the columns with
masking tape
or marker pen.
Right
Side
Left
Side
Front of
Rack
Rear of
Rack
Bottom of
HP NetServer
#
#
#
#
#
#
Masking
Tape
Marker
Figure 8-3. Location Marks on the Rack’s Columns
3. Mark the inside face of the left-rear and right-rear rack columns as shown
in Figure 8-3.
Attaching the Outer-Rail Assemblies
No tools are required to attach the outer-rail assemblies to the rack columns.
1. Pull the anti-tip foot forward out of the bottom of the rack.
See Figure 8-4 for the anti-tip foot location.
2. Lower the leveler screws on the racks lower four corners to make firm
contact with the floor. See Figure 8-4.
3. Align the left outer-rail to the left front and rear columns as shown in
Figure 8-4.