Fibre Channel ServerNet Adapter Installation and Support Guide (G06.27+, H06.03+)
Installing an FCSA
Fibre Channel ServerNet Adapter Installation and Support Guide—528254-011
2-5
Start Completing the Configuration Forms
This information is on the FCSAs physical label (see Figure 1-6 on page 1-10.)
2. Record the FCSA’s Physical Location on Your FCSA Configuration Form as 
described in Table 2-2
When an FCSA is installed, it is automatically assigned a name in the configuration 
database that is a concatenation of the following:
•
The name of the storage subsystem manager ($ZZSTO) 
•
The type of adapter (FCSA) 
•
The IOAM enclosure location (group, module, slot) where the adapter is 
installed 
For example, the name of the FCSA installed in slot 5 of the group 11 IOAM 
enclosure is: 
$ZZSTO.#FCSA.GRP-11.MOD-2.SLOT-5
This name is used in SCF STATUS and INFO commands and is displayed in the 
resulting reports of these commands.
3. Record the information for adding disks to the configuration database on your 
FCSA configuration form. Since you can have 512 of some of the disk attributes, 
extra forms are provided for these attributes in Appendix A, FCSA Configuration 
Forms for ESS Connections. Each of these forms provides space for recording 100 
of the various attributes. Print as many as you need for your configuration. 
Table 2-3 describes these attributes. (See the SCF Reference Manual for the 
Storage Subsystem for a full description of these attributes.) You need this 
information for the DISK Configuration (ESS Connection) procedure. 
Table 2-2. How to Fill in the Location of the FCSA
Field Where to Obtain the Information
Date Enter the date of when you are installing the FCSA
System Name Use the scroll keys on the LCD on the IO switch in the IOAM to 
scroll to the system name.
Group Number Use the scroll keys on the LCD on the IO switch in the IOAM to 
scroll to the group number information of the IOAM.
Module Number Possible module numbers are 2 and 3. See Figure 1-2
 on 
page 1-3 for an illustration of the modules in the IOAM.
Slot Number Check the slot number on the IOAM enclosure frame. The FCSA 
can be installed in slots 1, 2, 3, 4, and 5 of an IOAM. Since there 
are two IOAM logical modules in an IOAM enclosure, a total of 
10 FCSAs can be installed in an enclosure. Figure 1-2
 on 
page 1-3 shows these slot locations.