Updating Service Processor (SP) Firmware
G06.25 Software Installation and Upgrade Guide529430-001
7-23
Firmware Update for Fabric Side-Y (Using OSM)
The SP - Parameter Input dialog box appears. For example:
10. Enter the new file location. Use the $volume.subvolume.filename created
during the most recent DSM/SCM Build/Apply, and click OK. For example:
$system.sys01.spcode9
After you click OK, the number of SPs that are currently being updated appear in
the Running column under SP Firmware Update Progress. For example:
(Under Resource Name, the SP that has initially been updated displays a grey
checkmark beside it. The other SP, awaiting update, displays a yellow question
mark.)
11. To verify that firmware updates are in progress, select from Progress section,
Action Summary. The Action Status Summary window appears with information
about recent actions, including their status and overall progress.