NonStop S-Series Hardware Installation and FastPath Guide (G06.25+)

Troubleshooting
HP NonStop S-Series Hardware Installation and FastPath Guide529443-001
D-49
Configuring a ProCurve 24-Port Ethernet Switch
1. To access the switch’s configuration interface, open an Internet Explorer browser
window and enter the IP address of the switch in this form:
http://<ip address>.
2. In the configuration interface, select the Configuration tab, then select Port
Configuration.
3. Double-click the port being used for connectivity to the Ethernet port on the PMF
CRU.
4. Make sure Port Enabled is set to Yes.
5. Set Mode to 10HDx.
6. In the Broadcast Limit window, enter a value of 1.
7. Click Apply Settings (you may then close the switch configuration interface
window).
8. Repeat steps 1 through 7 for all other connections to PMFs on all of the switches.
Note. The switch requires a username and password for configuration changes. See
documentation shipped with the switch for the default values