NonStop S-Series Hardware Installation and FastPath Guide (G06.25+)
FastPath Tasks: Required
HP NonStop S-Series Hardware Installation and FastPath Guide—529443-001
E-26
4. Apply Power to Server
4. Apply Power to Server
1. Start with the highest-numbered group. Switch on its circuit breaker or plug the 
power shelf AC power cords into the designated AC receptacles. 
2. On the service side of the enclosure, check that the fans are operating by placing 
your hand over the exhaust grill. The fans should be turning, and you should hear 
air circulating through the enclosure. 
After a few seconds, if the fans do not operate, shut the system down quickly. See 
Power Is Applied to Enclosure But Fans Are Not Turning on page D-6.
3. Repeat Step 1 and Step 2 for all remaining enclosures without power shelves. 
Work in descending order of group number, ending with group 01.
4. During system startup, status LEDs on the various enclosures and CRUs light 
during a series of power-on self-tests (POSTs), which can take up to 10 minutes. 
All LEDs are lit briefly during POSTs, but only the green power-on LEDs should 
remain lit after the POSTs finish.
Before you start the system, ensure that POSTs have finished successfully. If the 
green power-on LED does not light or other LEDs remain lit, see Appendix D, 
Troubleshooting. 