Statements-7
Consumer Safety Statements
HIGH LEAKAGE CURRENT
To reduce the risk of electric shock due to high leakage currents, a reliable grounded
(earthed) connection should be checked before servicing power distribution unit.
Observe the following limits when connecting the product to AC power distribution
devices: For PDU that have attached AC power cords or are directly wired to the
building power, the total combined leakage current should not exceed 5 percent of the
rated input current for the device.
HIGH LEAKAGE CURRENT, EARTH CONNECTION ESSENTIAL BEFORE
CONNECTING SUPPLY”
“HOHER ABLEITSTROM. VOR INBETRIEBNAHME ERDUNGSVERBINDUNG
HERSTELLEN”
“COURANT DE FUITE E’LEVE’. RACCORDEMENT A LA TERRE INDISPENSABLE
AVANT LE RACCORDEMENT AU RESEAU”
FUSE REPLACEMENT
CAUTION – For continued protection Against Risk of Fire, Replace Only with Same
Fuse Type TCF15, Rated 600V~, 15A. Disconnect the interior AC power cord from the
PDU to the module before changing the fuse.
Consumer Safety Statements
Customer Installation and Servicing of Equipment
The following statements pertain to safety issues regarding customer installation and
servicing of equipment described in this manual.
•
Keep door closed for normal operation.
•
The equipment must be installed near the receptacles for the power cords, and the
receptacles must be easily accessible to the user.
WARNING. Do not touch the DC power connector on the NonStop S7400, S7600, or Sxx000
PMF CRU after you have unplugged the DC power cable from the CRU. It is possible to incur a
severe energy hazard for as long as fifteen (15) seconds after unplugging the cable. You can
make sure the CRU is safe to remove by testing (by using a volt meter) before touching the
pins on the DC power connector.