Installing Enclosures
HP NonStop S-Series Hardware Installation and FastPath Guide541880-002
2-26
Inspect the Components
a. Check that the ejectors on each ServerNet adapter in the enclosure are
latched.
b. If any ejectors are unlatched, reseat the ServerNet adapter as described next.
9. Perform these steps to reseat each ServerNet adapter that has become improperly
seated during shipping:
a. Put on your ESD wriststrap and attach the grounding clip securely to an
exposed, unpainted metal surface, such as the power interlock on a PMF CRU
or IOMF CRU.
b. Unlatch the ServerNet adapter ejector by pressing the blue-green tab and
pulling outward on the ejector to unseat the adapter. See Figure 2-22.
c. Grasp the ServerNet adapter ejector with one hand and slide the adapter
halfway out of the slot.
d. Reinsert the ServerNet adapter until the ejector on the adapter can be
engaged into the notch on the enclosure.
e. Latch the ServerNet adapter ejector by pressing the blue-green tab and then
closing the ejector to seat the adapter against the backplane.
10. Repeat Step 1 through Step 9 for all system enclosures.
Figure 2-22. Reseating a ServerNet Adapter
VST960.vsd