NonStop S-Series Hardware Installation and FastPath Guide (G06.29+)

Cabling Enclosures
HP NonStop S-Series Hardware Installation and FastPath Guide541880-002
3-4
2. Connect EPO Cables
2. Connect EPO Cables
1. Connect the unterminated end of an EPO cable to the appropriate junction box or
facility wiring.
2. Route the other end of this EPO cable to the service side of the system enclosure.
3. Attach the EPO cable connector to the EPO connector (slot 56) on the enclosure.
See Figure 3-2. The connector is designed to be attached only one way.
4. With the cable ties, secure the EPO cables for each enclosure to the cable
support.
5. Repeat Steps 1, 2, and 3 for all remaining system enclosures.
Caution. If you pass cables or cords through the handles of CRUs or FRUs, the cables or
cords might become unplugged during later replacement procedures. Do not use the handles
of CRUs or FRUs for cable management. See Figure 3-3
for proper cabling.
Figure 3-2. EPO Connector on a System Enclosure
56
Emergency Power-Off
(EPO) Connector
VST700.vsd