NonStop S-Series Hardware Installation and FastPath Guide (G06.29+)

Powering On and Starting the System
HP NonStop S-Series Hardware Installation and FastPath Guide541880-002
8-5
Powering On the System
5. Close the rear bezel door of the 519x module.
6. If the tape subsystem includes an automatic cartridge loader (ACL), install the
cleaning cartridge in the ACL. For instructions on installing the cleaning cartridge,
see the 5190/5194 Modular Tape Subsystem Manual.
You must install the cleaning cartridge before operating the ACL. If no cleaning
cartridge is installed, a CHK F8 check code appears on the ACL front panel when
the automatic cleaning routine is activated. Failing to install the cleaning cartridge
can cause dirt buildup on the read-write head.
7. Check the tape subsystem SCSI ID using the operator buttons on the tape drive or
ACL front panel. Reset the SCSI ID, if necessary, using the operator buttons. For
information on checking and setting the SCSI ID, see the 5190/5194 Modular Tape
Subsystem Manual.
Powering On the System
Fault Tolerance and Access to Power Cutoffs
Most NonStop S-series equipment supports two power cords. For fault tolerance,
do not plug the two power cords on any one piece of equipment into the same AC
receptacle. Plug each cord into a different receptacle that is connected to a
different breaker.
The AC receptacles to which the server is connected must be accessible to the
operator.
Alternatively, the branch circuit breaker supplying power to each receptacle must
be accessible to the operator and plainly marked to indicate which receptacle the
circuit breaker supports.
Figure 8-2. AC Power Switch for 519x Tape Drive
AC Power Switch
AC Power Cord
AC Power
Receptacle
Rear of 519x
Tape Drive
VST051.vsd