NonStop S-Series Hardware Installation and FastPath Guide (G06.29+)

FastPath Tasks: Required
HP NonStop S-Series Hardware Installation and FastPath Guide541880-002
E-22
2. Start the System
2. Start the System
1. Prepare for System Startup
1. If your system has multiple enclosures, verify that the ServerNet cables are
connected.
2. Verify that the following components are installed:
Task Page
1. Prepare for System Startup
E-28
2. Power On External System Devices E-23
3. Connect AC Power Cords E-24
Enclosures Without Power Shelves E-24
Enclosures With Power Shelves E-25
4. Apply Power to Server E-26
5. Verify Topology E-27
6. Verify System Components E-28
7. Start System E-28
Component Notes
All system enclosures N.A.
Power-on cables Not the same as the AC power cords. AC power cords
are not installed until you are ready to apply power to
the system.
Service-side enclosure doors Included with new system
Ethernet switch Must be connected to both the server and to the system
console
OSM or TSM Verify that the system console on which OSM or TSM is
installed is properly connected to the system
Emergency power-off (EPO)
cables
Within the United States, an EPO disconnect is required
in a system if the system is installed in a computer or
data processing room that is designed to comply with
the construction and fire-protection provisions of the
following:
NFPA-75, Protection of Electronic Computer/Data
Processor Equipment
Article 645, NFPA-70 (National Electric Code)
Outside the United States, an EPO disconnect is usually
not required unless specified by local authorities.
Tape drive Used for processor memory dumps