Introduction
HP NonStop S-Series Hardware Installation and FastPath Guide541880-002
1-23
Installation Overview
Groundstraps
What Groundstraps Do
Groundstraps:
Maintain the ground potential between NonStop S-series system enclosures
Protect the system from harmful electrical transients
Number of Groundstraps
For any system, the number of groundstraps required is equal to the number of
NonStop S-series enclosures minus one. For example, if a system contains six
enclosures, five groundstraps are required.
Where to Install Groundstraps
Groundstraps are installed between two enclosures, either in a stack or between
adjacent stacks. Groundstraps are not required between separate rows. For examples
of groundstrap locations for a variety of enclosure arrangements, see Figure 2-11 on
page 2-14 and Figure 2-12 on page 2-15.
A groundstrap connecting two system enclosures in a double-high stack might be
installed at the factory on a new system or an add-on enclosure. However, if you have
three or more enclosures, you must install the groundstraps that link the base
enclosures.
More About Groundstraps and Power Requirements
Groundstraps are installed on systems that have more than one enclosure.
Groundstraps are 14.8 inches (37.5 centimeters) long.
Note. For grounding information for IOAM enclosures, your service provider can refer to
the Modular I/O Installation and Configuration Guide located in the NTL Hardware Service
and Maintenance Collection in the Support and Service Library.