NonStop S-Series Operations Guide (G06.24+)
ServerNet Fabrics: Monitoring and Recovery
HP NonStop S-Series Operations Guide—522459-007
12-2
Monitoring the Status of the ServerNet Fabrics
Monitoring the Status of the ServerNet Fabrics
To monitor the status of the ServerNet fabrics:
•
Use the OSM Service Connection or the TSM Service Application to check the 
communication between processor enclosures, I/O enclosures, and systems. 
•
Use the Subsystem Control Facility (SCF) to check the status of interprocessor 
communication on the X and Y fabrics. 
Monitoring the ServerNet Fabrics Using OSM or TSM
To check the ServerNet fabrics:
1. Log on.
2. Expand the tree pane to locate and select the internal or external ServerNet fabric 
objects: 
a. The X and Y internal ServerNet fabric objects are located under the System 
object.
b. The X and Y external ServerNet fabric objects are located under the ServerNet 
Cluster object.
3. From the Attributes tab in the details pane:
a. For the internal ServerNet fabrics, verify that the Service State attribute is OK.
b. For the external ServerNet fabrics, verify that the Service State and 
Subcomponent State attributes are OK.