NonStop S-Series Planning and Configuration Guide (G06.26+)
Site Planning and Preparation
HP NonStop S-Series Planning and Configuration Guide—523303-017
12-8
Branch Circuits
Branch Circuits
Branch circuit requirements are:
•
All dedicated branch circuits supplying the system enclosures and tape drives must 
originate from the same branch circuit breaker panel. HP highly recommends that 
branch circuits for other peripheral equipment, such as system consoles, also 
originate from the same branch circuit breaker panel as that for system enclosures. 
This arrangement ensures a common ground reference for all enclosures, provides 
the best likelihood of homogeneous power failures, and minimizes noise and 
power transients. 
•
Each branch circuit must include a phase, a ground, and a neutral conductor. The 
ground conductor must be positioned inside the branch circuit conduit.
•
If duplex outlets are used, each half of each duplex outlet must be connected to a 
separate circuit. 
•
Two dedicated branch circuits are required for each system enclosure. Refer to 
Appendix B, Specifications, for more information about the power requirements for 
these circuits.
•
One dedicated branch circuit is required for each external tape drive. Refer to the 
documentation for the tape subsystem you are installing for information about the 
requirements for this circuit.
•
One dedicated branch circuit is required for each system console and each system 
console. HP recommends that each system console and workstation be provided 
with four receptacles originating from a single circuit breaker, so that related items, 
such as a large screen monitor, an Ethernet switch or hub, a modem, or a printer, 
can be easily connected. Normally, there are two system consoles on each 
system. 
•
System console outlet locations must be far enough away from enclosure outlet 
locations so that enclosure power cords will not be inadvertently plugged in to a 
system console outlet. Approximately 10 feet (3 meters) of separation is sufficient.
Uninterruptible Power Supplies (UPSs)
The power supplies in a system enclosure with a power shelf use power factor 
correction (PFC). The uninterruptible power supply (UPS) system you use must have a 
low output impedance to ensure the stability of AC power lines. The power supplies in 
a system enclosure with a power shelf have been designed to work with most UPS 
systems. However, if you choose a UPS system that uses ferroresonant transformers, 
you must ensure that it is designed to work with power supplies that use PFC.
The output voltage of the UPS must be sinusoidal with a total harmonic distortion 
(THD) of no more than 5 percent, and a distortion of any single harmonic of no more 
than 3 percent. Do not use UPS systems with a square or trapezoidal output voltage 
waveform.










