NonStop S-Series Planning and Configuration Guide (G06.26+)
Modular Power Information
HP NonStop S-Series Planning and Configuration Guide—523303-017
G-2
IOAM Enclosure Power Requirements
•
International - 200 to 250 V AC Cabinet Input Power
°
Single phase, three-wire with insulated ground conductor, 63A RMS
°
AC power cord (two supplied with cabinet): length: 7 ft. (183 cm)
°
AC power cable plug (two supplied per cabinet): three wire, single phase, 63A
°
HP part number: 527994-001
°
Manufacturer: Hubbell
°
HP-supplied plug manufacturer number: HBL363P6W
°
Required customer-supplied receptacle manufacturer number: 
HBL363C6W
Regardless of input power, each PDU supplies single-phase power at 200 to 250 V AC 
to each of its 14 receptacles and thereby to each enclosure that plugs into a 
receptacle. 
Maximum current requirement for the AC service depends on the number and type of 
enclosures installed in the modular cabinet.
IOAM Enclosure Power Requirements
Specifications in the following tables assume fully loaded IOAM enclosures.
IOAM Enclosure Power Specifications
IOAM Enclosure Inrush Current Specifications
Modular Unit
Plugs per 
Modular 
Unit
Total Power 
Consumption 
(Watts)
Maximum Total 
AC Current 
(Amps) per PDU 
@ 208 V AC
Maximum Total 
AC Current 
(Amps) per PDU 
@ 230 V AC
I/O adapter 
module (IOAM) 
Enclosure
4 824 5.3 4.8
Item
Peak Inrush Current 
(Amps) per 
Component Plug Average Inrush Current (Amps)
I/O adapter module (IOAM) 
Enclosure
 0 msec -- 1 msec 100 55
 1 msec -- 2 msec 55 33
 2 msec -- 10 msec 55 22
 10 msec -- 150 msec 25 15