NonStop S-Series Planning and Configuration Guide (G06.27+)

HP NonStop S-Series Planning and Configuration Guide523303-019
G-1
G Modular Power Information
This appendix provides information about topics:
Modular Cabinet Input Power
IOAM Enclosure Power Requirements
UPS Power Requirements
Power Distribution Unit Wiring
Modular Cabinet Input Power
Each modular cabinet contains two power distribution units (PDUs) with 14 power
receptacles per PDU (28 receptacles total). Input power per each PDU depends on the
site location
North America/Japan - 208 V AC Cabinet Input Power
°
Three-phase delta, four-wire with insulated ground conductor, 60A RMS
°
AC power cord (two supplied per cabinet): length 7 ft. (183 cm)
°
AC power cable plug (two supplied per cabinet): four wire, three phase, 60A
°
HP Part Number: 527993-001
°
Manufacturer: Hubbell
°
HP-supplied plug manufacturer number: HBL460P9W
°
Required customer-supplied receptacle manufacturer number:
HBL460C9W
Europe/Middle East/Africa - 230/400 V AC Cabinet Input Power
°
Three-phase wye, five-wire with insulated ground conductor, 63A RMS
°
AC power cord (two supplied with cabinet): length: 7 ft. (183 cm)
°
AC power cable plug (two supplied per cabinet): five wire, three phase, 63A
°
HP Part Number: 527995-001
°
Manufacturer: Hubbell
°
HP-supplied plug manufacturer number: HBL563P6W
°
Required customer-supplied receptacle manufacturer number:
HBL563C6W
Caution. The information in this section is for your guidance in planning the total power and
cooling requirements for your site. For complete information, consult the appropriate site
preparation or hardware manuals from HP or the original equipment manufacturer site.