NonStop S-Series Planning and Configuration Guide (G06.29+)
System Components
HP NonStop S-Series Planning and Configuration Guide—523303-021
4-23
SEBs and MSEBs
Selecting MSEB PICs
Ports on SEBs and MSEBs
Fabric Connections
For fault tolerance, SEBs and MSEBs are installed in an enclosure in pairs: one SEB 
or MSEB provides access to only the X fabric, and one provides access to only the Y 
fabric. 
ECL  The six-connector SEBs use the ECL interface. To connect MSEBs to six-
connector SEBs, select ECL PICs. 
Serial copper For new systems or extensive upgrading, select serial-copper PICs and 
use the slimmer, more flexible serial-copper cables.
MMF If enclosures are not arranged in conventional rows, select MMF PICs for 
distances of 200 meters (650 feet) between processor enclosures and 
between processor and I/O enclosures. Separation between enclosures is 
limited if you want all enclosures to be connected to the same power grid. 
MMF cabling is the preferred method of fiber-optic cabling. 
SMF If enclosures are not arranged in conventional rows or if you already have 
SMF cabling, select SMF PICs. NonStop S76000 and S86000 servers, and 
later, support SMF PICs for distances of 200 (650 feet) meters between 
processor enclosures or 5 km (3.1 mi) between processor and I/O 
enclosures. Separation between enclosures is limited if you want all 
enclosures to be connected to the same power grid. 
NNA The NNA PIC is configured to operate with the HP NonStop Metro Cluster 
product. The NNA PIC uses the SMF interface.
VST015.vsd
MSEB
ECL
PIC
Serial
Copper
(Fixed)
SEB
ECL
Serial
Copper
PIC
MMF PIC,
SMF PIC,
and NNA PIC