NonStop S-Series Planning and Configuration Guide (G06.29+)

Specifications
HP NonStop S-Series Planning and Configuration Guide523303-021
B-6
Fiber-Optic Cables
Fiber-Optic Cables
The minimum bend radius for SMF and MMF fiber-optic cables is:
Unsheathed: 1.7 inch (4.3 cm)
Sheathed (ruggedized): 4.2 inch (10.7 cm)
You can use fiber-optic cables available from HP or you can provide your own fiber-
optic cables.
If you provide your own fiber-optic cables, the attenuation specification is:
3.5 db/km of length
0.5 db/connector insertion
10.5 db maximum allowable loss for any link
You or your installer should verify that the link does not exceed the maximum allowable
loss by using a calibrated optical power source to measure the optical power at the
distant end of the cable and calculating the attenuation.
Any loss of 10.5 db or less is acceptable. Any attenuation above 10.5 db might appear
to work, but the bit error rate will be unacceptable and you must repair or replace the
cable.
Modified System Enclosures
A modified system enclosure has two pins cut and removed from the backplane
connector in slot 55, correcting a design defect when the enclosure is populated with
IOMF CRUs. A modified enclosure is identified by a revision label on the cable-
management post.
A modified enclosure cannot be used with S7000, S7400, S70000, or S72000 PMF
CRUs but can be used with S7600 or later and S74000 or later PMF CRUs, IOMF
CRUs, or IOMF 2 CRUs.