NonStop S-Series Planning and Configuration Guide (G06.29+)

Specifications
HP NonStop S-Series Planning and Configuration Guide523303-021
B-11
AC Power Requirements for One System Enclosure
AC Power Requirements for One System Enclosure
Note the following about NonStop S-series power supplies:
Auto-ranging power supplies automatically configure themselves for either 100-
120 V AC or 200-240 V AC operation upon application of AC power.
The power supplies for enclosures without power shelves are contained within the
PMF CRUs and the IOMF CRUs.
The power supplies for enclosures with power shelves are independent CRUs
contained in the power shelf section of the enclosure.
Environmental Specifications for One System Enclosure
Factor 100-120 Volts AC Operation 200-240 Volts AC Operation
Nominal voltage 100-120 V AC 200-240 V AC
Line frequency 50/60 Hz nominal 50/60 Hz nominal
Voltage tolerance 85-132 V AC 170-264 V AC
Frequency tolerance 47-63 Hz 47-63 Hz
Branch circuits 2 for each enclosure 2 for each enclosure
Amperage 20 A 10 A
Branch circuit rating Without power shelf: 15 A
With power shelf: 20 A
10 A
Inrush input current Without power shelf: 40 A peak
With power shelf: 80 A peak
Nominal VA 600 VA for each power cord
(1200 VA total)
600 VA for each power cord
(1200 VA total)
Heat output Without power shelf: 960 W
(3275 Btu/h)
With power shelf: 1600 W
(5456 Btu/h)
Without power shelf: 960 W
(3275 Btu/h)
With power shelf: 1600 W (5456
Btu/h)
Temperature Operating 40 to 100 °F (5 to 38 °C)
Up to 72-hour storage -40 to 150 ° F (-40 to 66 °C)
Up to 6-month storage -20 to 131 °F (-29 to 55 ° C)
Relative Humidity Operating 10% to 85%, noncondensing
Nonoperating 10% to 95%, noncondensing
Power Dissipation Without power shelf 960 W (3275 Btu/h)
With power shelf 1600 W (5456 Btu/h)
Altitude Operating 0 to 10,000 feet (0 to 3,048 meters)
Nonoperating 0 to 40,000 feet (0 to 12,192 meters)
Noise 60 dB(A)