NonStop S-Series Planning and Configuration Guide (G06.29+)
Specifications
HP NonStop S-Series Planning and Configuration Guide—523303-021
B-11
AC Power Requirements for One System Enclosure
AC Power Requirements for One System Enclosure
Note the following about NonStop S-series power supplies:
•
Auto-ranging power supplies automatically configure themselves for either 100-
120 V AC or 200-240 V AC operation upon application of AC power.
•
The power supplies for enclosures without power shelves are contained within the
PMF CRUs and the IOMF CRUs.
•
The power supplies for enclosures with power shelves are independent CRUs
contained in the power shelf section of the enclosure.
Environmental Specifications for One System Enclosure
Factor 100-120 Volts AC Operation 200-240 Volts AC Operation
Nominal voltage 100-120 V AC 200-240 V AC
Line frequency 50/60 Hz nominal 50/60 Hz nominal
Voltage tolerance 85-132 V AC 170-264 V AC
Frequency tolerance 47-63 Hz 47-63 Hz
Branch circuits 2 for each enclosure 2 for each enclosure
Amperage 20 A 10 A
Branch circuit rating Without power shelf: 15 A
With power shelf: 20 A
10 A
Inrush input current Without power shelf: 40 A peak
With power shelf: 80 A peak
Nominal VA 600 VA for each power cord
(1200 VA total)
600 VA for each power cord
(1200 VA total)
Heat output Without power shelf: 960 W
(3275 Btu/h)
With power shelf: 1600 W
(5456 Btu/h)
Without power shelf: 960 W
(3275 Btu/h)
With power shelf: 1600 W (5456
Btu/h)
Temperature Operating 40 to 100 °F (5 to 38 °C)
Up to 72-hour storage -40 to 150 ° F (-40 to 66 °C)
Up to 6-month storage -20 to 131 °F (-29 to 55 ° C)
Relative Humidity Operating 10% to 85%, noncondensing
Nonoperating 10% to 95%, noncondensing
Power Dissipation Without power shelf 960 W (3275 Btu/h)
With power shelf 1600 W (5456 Btu/h)
Altitude Operating 0 to 10,000 feet (0 to 3,048 meters)
Nonoperating 0 to 40,000 feet (0 to 12,192 meters)
Noise 60 dB(A)