NonStop S-Series Planning and Configuration Guide (G06.29+)

Specifications
HP NonStop S-Series Planning and Configuration Guide523303-021
B-18
AC Power Requirements for a Modular Cabinet
AC Power Requirements for a Modular Cabinet
This subsections contains:
PDU Power Configurations on page B-18
Modular Cabinet AC Power
on page B-18
Modular Cabinet Modules AC Power
on page B-19
PDU Power Configurations
Modular Cabinet AC Power
Geography Configuration
USA, Japan 208 VAC, three phase delta, 60 A RMS, 4 wire
EMEA 230/400 VAC, three phase wye, 63 A RMS, 5 wire
EMEA 230/400 VAC, three phase wye, 63 A RMS, 5 wire, harmonized
WW 200 to 250 VAC, single phase, 63 A RMS, 3 wire
WW 200 to 250 VAC, single phase, 63 A RMS, 3 wire, harmonized
Factor
208 VAC, three-
phase delta, 4-wire
PDU (North
America, Japan)
230/400 VAC, three-
phase wye, 5-wire
PDU (EMEA)
200 to 250 VAC,
single-phase PDU
(worldwide)
Nominal voltage 208 VAC 230 VAC 240 VAC
Line frequency 50/60 Hz 50/60 Hz 50/60 Hz
Voltage tolerance 200-264 VAC 200-264 VAC 200-264 VAC
Frequency tolerance 47-63 Hz 47-63 Hz 47-63 Hz
Branch circuit yes yes yes
Branch circuit rating 12 A 12 A 12 A
Amperage 60 A 63 A 63 A
Nominal VA 12,480 VA 14,490 VA 15, 120 VA