NonStop S-Series Planning and Configuration Guide (G06.29+)

Specifications
HP NonStop S-Series Planning and Configuration Guide523303-021
B-19
AC Power Requirements for a Modular Cabinet
Modular Cabinet Modules AC Power
Factor
IOAM
Enclosure
Maintenance
switch
R5500XR UPS
(North America,
Japan)
R5500XR UPS
(International)
Nominal
voltage
208/230/240
VAC
208/230/240
VAC
208/230/240 VAC 208/230/240 VAC
Line
frequency
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Voltage
tolerance
200-264 VAC 200-264 VAC 200-264 VAC 200-264 VAC
Frequency
tolerance
47-63 Hz 47-63 Hz 47-63 Hz 47-63 Hz
Amperage 2.5 A @
200 VAC
per side
1.2 A @
200 VAC
per side
22.5 A @
200 VAC
per side
22.5 A @
200 VAC
per side
Nominal VA 500 276 5000 5000
Heat output
BTU/hr
2008 123 629 online
2730 on battery
629 online
2730 on battery
Inrush
current, fully
populated
enclosure
<80 A <50 S <120 A <120 A