NonStop S-Series Planning and Configuration Guide (G06.29+)

System Name
/ /
Date
of
Page
Cross-Row Cabling Worksheet, SEB to SEB
31 inches (cabinet depth), 6 inches of slack (3 inches per cable end)
Standard Measurements
to groupFrom group
Width of service aisle (48 inches minimum)
If the cable is installed under a raised floor:
Variable Measurements
+
Distance from bottom of base enclosure to subfloor, multiply by 2
+
If cable runs in overhead cable trough
Distance from top of cabinet to cable trough, multiply by 2
+
VST378.vsd
-
If the enclosures are placed with their appearance sides facing each other, add
31 inches
If the enclosures are placed with their service sides facing each other,
subtract 31 inches
To a horizontally adjacent enclosure, 63 inches
To a vertically adjacent enclosure, 99 inches
To a diagonally adjacent enclosure, 99 inches
For each additional intervening enclosure, add 23 inches
If you tie the cable down, then stretch it across the service side of its enclosure to the other
cable trough before routing it across a row to another enclosure, add the appropriate length:
Total Cable Length
+
+
+
Cable Part Number
If this cable will be bundled with a large number of other cables, add extra slack.
+
a base enclosure in a double-high stack, add 25 inches
If cable originates from:
a stacked enclosure, add 59 inches
+
a base enclosure in a double-high stack, add 25 inches
If cable inserts in:
a stacked enclosure, add 59 inches
+
a base enclosure in a double-high stack, add 25 inches
If cable originates from:
a stacked enclosure, add 20 inches
+
a base enclosure in a double-high stack, add 25 inches
If cable inserts in:
a stacked enclosure, add 54 inches
+
37
+