NonStop S-Series Planning and Configuration Guide (G06.29+)

HP NonStop S-Series Planning and Configuration Guide523303-021
G-1
G Modular Power Information
This appendix provides information about topics:
Modular Cabinet Input Power
IOAM Enclosure Power Requirements
UPS Power Requirements
Power Distribution Unit Wiring
Modular Cabinet Input Power
Each modular cabinet contains two power distribution units (PDUs) with 14 power
receptacles per PDU (28 receptacles total). Input power per each PDU depends on the
site location
North America and Japan: 208 V AC PDU Power Cords
Three-phase delta, four-wire with insulated ground conductor, 60A (or optional
30A) RMS
AC power cord (two supplied per modular cabinet): length 7 feet (183 centimeters)
60A AC power cable plug (one per power cord): four-wire, three-phase
°
HP Product ID: M8950-4
°
HP part number: 527993
°
Manufacturer: Hubbell
°
HP supplied plug manufacturer number: HBL460P9W
°
Required customer-supplied receptacle manufacturer number: HBL460C9W or
equivalent receptacle
30A AC power cable plug (one per power cord): four-wire, three-phase
°
HP Product ID: not available
°
HP part number: 5541088
°
Manufacturer: Hubbell
°
HP supplied plug manufacturer number: HBL2721
°
Required customer-supplied receptacle manufacturer number: HBL2720 (wall
mount recepticle), HBL2723 (connector body for cable), or equivalent
receptacle
Europe, Middle East, and Africa: 230/400 V AC PDU Power Cords
Three-phase wye, five-wire with insulated ground conductor, 63A (or optional 30A)
RMS
AC power cord (two supplied per modular cabinet): length 7 feet (183 centimeters)
60A AC power cable plug (one per power cord): five-wire, three-phase, 63A
Caution. The information in this section is for your guidance in planning the total power and
cooling requirements for your site. For complete information, consult the appropriate site
preparation or hardware manuals from HP or the original equipment manufacturer site.