NonStop S-Series Planning and Configuration Guide (G06.29+)

Modular Power Information
HP NonStop S-Series Planning and Configuration Guide523303-021
G-3
IOAM Enclosure Power Requirements
30A nonharmonized AC power cable plug (one per power cord): three-wire, single-
phase,
°
HP Product ID: not available
°
HP part number: 541087
°
Manufacturer: Hubbell
°
HP supplied plug manufacturer number: HBL2621
°
Required customer-supplied receptacle manufacturer numbers: HBL2620 (wall
mount recepticle), HBL2623 (connector body for cable), or equivalent
receptacle
Regardless of input power, each PDU supplies single-phase power at 200 to 250 V AC
to each of its 14 receptacles and thereby to each enclosure that plugs into a
receptacle.
Maximum current requirement for the AC service depends on the number and type of
enclosures installed in the modular cabinet.
IOAM Enclosure Power Requirements
Specifications in the following tables assume fully loaded IOAM enclosures.
IOAM Enclosure Power Specifications
IOAM Enclosure Inrush Current Specifications
Modular Unit
Plugs per
Modular
Unit
Total Power
Consumption
(Watts)
Maximum Total
AC Current
(Amps) per PDU
@ 208 V AC
Maximum Total
AC Current
(Amps) per PDU
@ 230 V AC
I/O adapter
module (IOAM)
Enclosure
4 824 5.3 4.8
Item
Peak Inrush Current
(Amps) per
Component Plug Average Inrush Current (Amps)
I/O adapter module (IOAM)
Enclosure
0 msec -- 1 msec 100 55
1 msec -- 2 msec 55 33
2 msec -- 10 msec 55 22
10 msec -- 150 msec 25 15