NonStop S-Series Planning and Configuration Guide (G06.29+)

Modular Power Information
HP NonStop S-Series Planning and Configuration Guide523303-021
G-4
UPS Power Requirements
UPS Power Requirements
Specifications in the following tables assume the UPS is integrated in the modular
cabinet.
UPS Power Specifications
UPS Inrush Current Specifications
Model R5500 XR UPS
Power Distribution Unit Wiring
Each modular cabinet has two power distribution units (PDUs). The PDUs are installed
at the factory with the junction boxes either at the top or bottom, depending on whether
the AC power is delivered from above or below.
Additionally, the wires inside the PDU are strapped, within the junction box, to meet the
customers specifications. The orientation of the PDUs and the strapping of the PDU
wires are not expected to be changed in the field.
Modular Unit
Plugs per
Modular
Unit
Total Power
Consumption
(Watts)
Maximum Total
AC Current
(Amps) per PDU
@ 208 V AC
Maximum Total
AC Current
(Amps) per PDU
@ 230 V AC
UPS, R5500 XR,
0-1 cycle
(operates at 95%
efficiency)
2 230 1.1 (estimated
maximum)
1.0 (estimated
maximum)
Item
Peak Inrush Current
(Amps) per
Component Plug Average Inrush Current (Amps)
UPS, R5500 XR, 0-1 cycle 250
Version
Operating Voltage
Settings
Power Out
(VA/Watts) Input Connection
North America and Japan 200/208*, 220, 230, 240 5000/4500 L6-30P
International 220, 230*, 240
If set at:
200/208
6000/5400
Then:
500/4500
IEC-309 32 Amp
* Factory default setting