NonStop S-Series Planning and Configuration Guide (G06.29+)
Modular Power Information
HP NonStop S-Series Planning and Configuration Guide—523303-021
G-4
UPS Power Requirements
UPS Power Requirements
Specifications in the following tables assume the UPS is integrated in the modular 
cabinet.
UPS Power Specifications
UPS Inrush Current Specifications
Model R5500 XR UPS
Power Distribution Unit Wiring
Each modular cabinet has two power distribution units (PDUs). The PDUs are installed 
at the factory with the junction boxes either at the top or bottom, depending on whether 
the AC power is delivered from above or below. 
Additionally, the wires inside the PDU are strapped, within the junction box, to meet the 
customer’s specifications. The orientation of the PDUs and the strapping of the PDU 
wires are not expected to be changed in the field.
Modular Unit
Plugs per 
Modular 
Unit
Total Power 
Consumption 
(Watts)
Maximum Total 
AC Current 
(Amps) per PDU 
@ 208 V AC
Maximum Total 
AC Current 
(Amps) per PDU 
@ 230 V AC
UPS, R5500 XR, 
0-1 cycle 
(operates at 95% 
efficiency)
2 230 1.1 (estimated 
maximum)
1.0 (estimated 
maximum)
Item
Peak Inrush Current 
(Amps) per 
Component Plug Average Inrush Current (Amps)
UPS, R5500 XR, 0-1 cycle 250 —
Version
Operating Voltage 
Settings
Power Out 
(VA/Watts) Input Connection
North America and Japan 200/208*, 220, 230, 240 5000/4500 L6-30P
International 220, 230*, 240
If set at: 
200/208
6000/5400
Then:
500/4500
IEC-309 32 Amp
* Factory default setting