installed.
Insert the FCSA:
Using both hands, hold the FCSA so that its ejector is at the top.a.
Insert the adapter into its slot in the enclosure.b.
Firmly push the FCSA to the rear of its slot, but do not force it.
Caution: To avoid damaging the connector pins, apply equal pressure to both the
top and bottom of the FCSA when pushing it into its slot. If you try to
push the FCSA into its slot when the pins in either the FCSA or the
midplane are damaged, you must replace both the FCSA and the
enclosure.
c.
Press down and back on the ejector. The ejector will slide under the top lip of the frame
and secure the adapter in place.
d.
5.
Disconnect the grounding clip of your ESD wrist strap from the rack or enclosure.6.
Connect the Fibre Channel cables to the Fibre Channel ports on the FCSA by lining up the
retaining clips with the ports and gently inserting them into the ports, one at a time.
The green power-on LED at the bottom of the adapter should now be lit. If the LED is not lit,
either reseat the FCSA or install a different FCSA.
7.
After you install the new FCSA, refer to the Fibre Channel ServerNet Adapter Installation and
Support Guide for information about resuming operations.
8.
Once you confirm that the FCSA has been replaced, OSM presents these options for bringing up the
paths associated with this adapter:
Bring up and balance. This option makes the -P (primary) and -M (mirror) paths active.
Bring up only. This option starts the path only if the other path is already up.
Leave down.
FCSA FSAC
Attributes
Actions
A Fibre Channel SAC (ServerNet addressable controller) is one of two fiber-optic plug-in cards
mounted on an FCSA (Fibre Channel ServerNet adapter).
Location in OSM Tree: System > Group > IOAM Enclosure > IOAM > FCSA > FCSA FSAC
Example: FCSA FSAC (100.2.1.1)