OSM Service Connection User's Guide (G06.30+)

Actions
Disable ServerNet Port
Disables the specified ServerNet router port on this CRU. Perform this action only as directed by
OSM alarm repair actions.
Parameter: Port Number
Enable ServerNet Port
Enables the specified ServerNet router port on this CRU. Perform this action only as directed by
OSM alarm repair actions.
Parameter: Port Number
Force Power Off
Use this action to power off the CRU and all of its subcomponents only if the Prepare to Power Off
or Power Off actions fail. The Force Power Off does not perform the other precautionary checks that
are done by the Prepare to Power Off and Power Off actions. However, these steps are taken:
If the SP on this IOMF CRU is designated as Active (Primary), resets the SP so the peer SP
becomes primary instead
Disables the battery
Power Off
Upon successful completion of the Prepare to Power Off action, you can use the Power Off action to
turn off power to the IOMF CRU and all components.
The Power Off action first checks to ensure that the other IOMF CRU in this enclosure exists and is
powered on. If the check is completed successfully, the CRU is powered off. If the check fails, the
CRU remains powered.
The Power Off action does not disable the battery or switch the SP status to Active Secondary. Use
the Prepare to Power Off action to perform these operations before using the Power Off action.
Prepare to Power Off
Performs precautionary check to ensure that it is safe to power off the group and performs steps to
prepare the group for the Power Off action.
The precautionary check ensures that the other IOMF CRU in this enclosure exists and is powered
on.
If the check fails, the Prepare to Power Off action fails and the steps that follow are not taken. If the
check confirms that it is safe to power off, these preparatory steps are performed:
If the SP on this IOMF is designated as Active Primary, resets the SP so that the peer SP