ServerNet Cluster 6770 Hardware Installation and Support Guide
Troubleshooting
ServerNet Cluster 6770 Hardware Installation and Support Guide—522544-002
8-24
Recovery Procedures for the ServerNet II Switch
4. Inspect each fiber-optic cable connector. See Figure 8-8.
•
Make sure the ferrule housing and the ceramic ferrule tip are visible. The
ferrule housing should be at least flush with the connector housing.
•
It is normal for the ferrule housing to slide freely (approximately 2 mm) within
the connector body between the stops designed into the connector body
assembly.
•
If the ferrule housing and ceramic ferrule tip are pushed back inside the
connector body, the connector might be defective and you should obtain
another cable.
5. Align the keys on the connector body with the key slots on the receptacle of the
ServerNet II Switch. The key slots on ports 8 through 11 is located on the top of the
receptacle. This is opposite the key slots on ports 0 through 7, which are on the
bottom of the receptacle.
Figure 8-8. Inspecting Fiber-Optic Cable Connectors
VST003.vsd